INSPECTION & TESTING SPECIFICATIONS FOR WET PIPE FIRE SPRINKLER SYSTEMS

  • System inspected according to NFPA 25 standards on a yearly, quarterly, and monthly basis
  • Check piping for mechanical damage, loose hangers, and leaks where it is possible to do so
  • The fire department Siamese connection is checked to see if it is free of debris and that it has the proper caps and gaskets
  • Main drain test performed – involves a full flow through the system’s main drain with the static and residual pressures recorded
  • Water will be flowed through the inspector’s test valve to ensure proper delivery through the system
  • All alarms including the flow switch, motor gongs, pressure alarms, etc … will be tested
  • Antifreeze loop, if present, will be tested for proper mixture of water and antifreeze – the antifreeze loop should be drained, remixed, and pumped back in annually to ensure that the piping will not freeze.
  • Sprinkler heads are checked for obvious mechanical damage, corrosion, paint, leaks, and any other factor that may impair proper function
  • Ensure proper sprinkler head application and head temperature rating
  • Identify recalled sprinkler heads
  • Check for proper storage height for sprinkler heads
  • Tag and date riser for Fire Marshall and insurance agency
  • A printed report of the status of the fire sprinkler system is provided
  • Complete all necessary forms and supply copies to building occupant
  • Light maintenance problems are fixed